Solar string sizing calculator

Find how many panels you can wire in series on one inverter input. Too many and the voltage on a freezing morning can exceed the inverter's limit and damage it. Too few and on a hot afternoon the voltage can fall below the range where the inverter harvests power.

V

Open-circuit voltage from the panel datasheet.

%/°C

From the datasheet, usually −0.25 to −0.35. Enter %/°C, not V/°C.

°C

Record low (or extreme minimum design temperature) for the site.

V

The absolute maximum, e.g. 600 or 1000 V, not the top of the MPPT range.

Optional: shortest string

V

Maximum-power voltage from the datasheet.

V

Lowest voltage at which the inverter still tracks maximum power.

Panels per string

5–11 panels

Panel Voc at -10°C
54.2 V
Maximum panels in series
11
String Voc in the cold (at max)
596.0 V
Panel Vmp at 70°C cell
35.0 V
Minimum panels in series
5

How it works

Panel voltage changes with temperature: it rises in the cold and falls in the heat. Datasheet voltages are measured at 25°C (standard test conditions, STC), so the calculator corrects them for the coldest and hottest conditions.

  1. Cold Voc. Raise the open-circuit voltage for the lowest temperature. The coefficient is negative, so a temperature below 25°C increases the voltage.

    Voc cold = Voc × (1 + (T min − 25) × coefficient ÷ 100)

  2. Longest string. Divide the inverter maximum by the cold Voc and round down, because one panel more would exceed the limit.

    Max panels = floor(V max inverter ÷ Voc cold)

  3. Hot Vmp (optional). Lower the maximum-power voltage for a 70°C cell, using a typical coefficient of -0.35%/°C.

    Vmp hot = Vmp × (1 + (70 − 25) × (-0.35) ÷ 100)

  4. Shortest string (optional). Divide the MPPT minimum by the hot Vmp and round up, because one panel fewer would drop below it.

    Min panels = ceil(V MPPT min ÷ Vmp hot)

Any string length from the minimum to the maximum works for voltage. Leave the optional fields empty to get only the maximum.

The inputs

Panel Voc (STC)
Open-circuit voltage: the voltage of the panel with nothing connected, from the datasheet. This is the highest voltage the panel produces.
Voc temperature coefficient
How much Voc changes per degree, in %/°C. Typical values are −0.25 to −0.35. If the datasheet gives mV/°C, divide by Voc in volts and by 10 to get %/°C. The sign does not matter here; cold always raises Voc.
Lowest expected temperature
The coldest air temperature at the site, such as the record low or the extreme minimum design temperature published for the location.
Inverter maximum DC input voltage
The absolute limit on the inverter or charge controller datasheet, often 150, 450, 600 or 1000 V. Never exceed it.
Panel Vmp (optional)
Voltage at maximum power, from the datasheet. This is the voltage the panel runs at while producing.
MPPT minimum voltage (optional)
The lowest string voltage at which the inverter still finds the maximum power point. Below it, output drops.

Worked example

A panel with Voc 49.5 V, Vmp 41.6 V and a Voc coefficient of -0.27%/°C goes on an inverter with a 600 V maximum and a 150 V MPPT minimum. The record low at the site is -10°C.

  1. Cold Voc: 49.5 × (1 + (-10 − 25) × (-0.27) ÷ 100) = 49.5 × 1.0945 = 54.18 V.
  2. Longest string: 600 ÷ 54.18 = 11.07, rounded down to 11 panels (596.0 V in the cold).
  3. Hot Vmp: 41.6 × (1 + (70 − 25) × (-0.35) ÷ 100) = 41.6 × 0.8425 = 35.05 V.
  4. Shortest string: 150 ÷ 35.05 = 4.28, rounded up to 5 panels.

Any string of 5 to 11 panels stays within the inverter's voltage limits. The calculator above opens with these values.

Assumptions and limits

  • Cold cells are at air temperature. At first light on a still, frosty morning, panels sit at about the air temperature while sunlight starts producing voltage. This is the worst case for Voc.
  • Straight-line temperature correction using the datasheet coefficient, as NEC 690.7(A) allows. The NEC's alternative table of correction factors can give a slightly different answer; follow whichever method your inspector requires.
  • Fixed hot-day values. Cell temperature 70°C and a Vmp coefficient of -0.35%/°C. Flush roof mounts with little airflow and very hot climates can run hotter, and your panel's Vmp coefficient may differ; add a panel to the minimum if you are close.
  • Identical panels, one string per input. All panels in the string are the same model and orientation.
  • Voltage only. Not checked: the inverter's maximum input current per MPPT (Isc), how many strings can go in parallel, start-up voltage, DC-to-AC ratio, optimizers or microinverters, and bifacial gain.

Common questions

How many solar panels can I connect in series?

As many as fit under the inverter's maximum DC voltage on the coldest morning, when panel voltage is highest. A panel with a Voc of 49.5 V and a -0.27%/°C coefficient reaches 54.2 V at -10°C, so up to 11 fit on a 600 V inverter and 18 on a 1000 V inverter.

Why does panel voltage go up in cold weather?

Solar cells produce a higher voltage when they are cold. Datasheets give Voc at 25°C, and the temperature coefficient (around −0.25 to −0.30 %/°C for modern panels) says how much it rises for each degree colder. A string that is fine at 25°C can exceed the inverter limit on a freezing sunny morning and damage it.

Should I wire solar panels in series or parallel?

Series adds voltage and keeps current the same, so cables stay thinner and grid-tied inverters reach their MPPT range. Parallel adds current at the same voltage, which suits low-voltage charge controllers and reduces the effect of shading on one panel. Most systems use series strings, then parallel strings if the inverter input allows the current.

Next, size the cable from the array to the inverter with the wire size calculator.

Use it on the roof

The string sizing calculator is also in the Solar Calibrator app, with the same formulas, offline use, PDF reports, and tilt, orientation, battery and load tools.