Solar DC wire size calculator

Find the smallest standard cable for a DC circuit, such as panels to charge controller or battery to inverter. It checks two things: the voltage lost along the cable, and the current the cable can carry safely.

V

Nominal DC voltage of the circuit, e.g. 12, 24, 48.

A

Maximum continuous current. For PV source circuits, enter 1.25 × Isc (see assumptions).

m

Distance from source to load. The return conductor is counted for you.

Length unit
%

3% is a common target for solar and battery circuits.

Conductor

Recommended cable

10 mm²

Copper, 6 AWG

AWG equivalent
6 AWG
Minimum area for voltage drop
9.58 mm²
Design current (× 1.25)
25.0 A
Voltage drop at this size
2.87% (0.69 V)
Size set by
Voltage drop

How it works

A cable is a long, thin resistor. The longer and thinner it is, the more voltage it wastes as heat. The calculator does three steps:

  1. Area for voltage drop. Work out the cross-section needed to keep the drop under your limit. Current flows out and back, so the length is doubled.

    A (mm²) = 2 × L × I × ρ ÷ (V × drop% ÷ 100)

  2. Current to carry. Multiply the current by 1.25 so the cable is not run at its limit for hours on end.

    I design = I × 1.25

  3. Pick a standard size. Take the smallest size in the table that has at least the area from step 1 and a current rating of at least the design current. Whichever check needs the bigger cable decides the size.

It then reports the voltage drop you get with the chosen size, which is lower than your limit because standard sizes come in steps.

The inputs

System voltage (V)
The nominal DC voltage of the circuit: 12, 24 or 48 V for a battery bank, or the string voltage for a panel run. Lower voltage needs thicker cable for the same power.
Current (I)
The highest current the cable will carry continuously, in amps. For a battery to inverter cable, use inverter power ÷ battery voltage ÷ inverter efficiency.
Cable length (L)
One-way distance from source to load. Do not double it; the formula already counts the return conductor.
Maximum voltage drop
How much of the voltage you accept losing in the cable. 3% is a common target; 1 to 2% suits low-voltage battery cables where every volt counts.
Conductor
Copper or aluminum. Aluminum has about 1.6 times the resistance of copper, so it needs a larger size.

Worked example

A 24 V battery feeds a load drawing 20 A through 10 m of copper cable, with a 3% drop limit.

  1. Allowed drop: 24 V × 3% = 0.72 V.
  2. Area for that drop: 2 × 10 × 20 × 0.01724 ÷ 0.72 = 9.58 mm².
  3. Design current: 20 A × 1.25 = 25 A.
  4. Smallest metric size with at least 9.58 mm² and 25 A: 10 mm² (rated 63 A). Smallest AWG size: 6 AWG (13.3 mm², rated 65 A). Voltage drop decided the size here, not current.
  5. Drop with 10 mm²: 2 × 10 × 20 × 0.01724 ÷ 10 = 0.69 V (2.87%), inside the 3% limit.

Assumptions and limits

  • DC, two wires. One positive and one negative conductor of the same size. Not for AC circuits, where power factor and three-phase wiring change the formula.
  • Resistance at 20°C. Copper 0.01724 Ω·mm²/m, aluminum 0.0282 Ω·mm²/m. A warm cable has more resistance (roughly 20% more at 70°C), so the real drop is a little higher. Leave margin if the result is close to your limit.
  • 125% of the current you enter. For PV source and output circuits, NEC 690.8 first sets the maximum current at 125% of the panels' short-circuit current (Isc), then sizes conductors at 125% of that. Enter 1.25 × Isc to get both factors (156% of Isc).
  • Current ratings from standard tables, no derating. Metric sizes use IEC 60364-5-52, method C (clipped to a surface), PVC insulation, two loaded conductors, 30°C air. AWG sizes use NEC Table 310.16, 75°C column. Hot roofs, conduit, bundled cables and other insulation types change these ratings and can call for a larger cable.
  • Not checked: overcurrent protection, terminal temperature ratings, minimum sizes required by code, and short-circuit withstand.
  • Table range. Copper 1.5 to 120 mm², aluminum 16 to 120 mm² (16 mm² is the usual smallest aluminum cable), AWG 14 to 4/0. Above that the calculator says so instead of guessing.
  • The drop limit is a design choice. Most codes do not set one for DC; the NEC suggests 3% for a branch circuit in an informational note.
Cable tables used
Metric, current rating (A)
mm²CopperAluminum
1.519.5—
2.527—
436—
646—
1063—
168566
2511283
35138103
50168125
70213160
95258195
120299226
AWG, current rating (A)
AWGmm²CopperAluminum
142.0820—
123.312520
105.263530
88.375040
613.36550
421.28565
326.710075
233.611590
142.4130100
1/053.5150120
2/067.4175135
3/085200155
4/0107.2230180

Common questions

What size wire do I need from solar panels to the charge controller?

It depends on current, voltage and distance. For two panels in series (about 36 V) with a short-circuit current of 10 A, 15 m from the charge controller, enter 1.25 × 10 = 12.5 A and a 3% drop limit. The calculator picks 6 mm² (8 AWG) copper, with voltage drop deciding the size. Higher-voltage strings need much thinner cable for the same power.

What gauge wire for a 3000 W inverter?

A 3,000 W inverter at 90% efficiency draws 139 A from a 24 V battery and 69 A from a 48 V battery. For a 2 m run with a 2% drop limit, that needs 70 mm² (2/0 AWG) copper at 24 V, or 25 mm² (3 AWG) at 48 V. At 12 V it would draw 278 A, more than the largest cable in the table (120 mm², 4/0 AWG) can carry, which is why inverters this size usually run on 24 or 48 V.

How much voltage drop is acceptable in a solar system?

Up to 3% is a common target for panel runs. For low-voltage battery and inverter cables, 1 to 2% is better, because every volt lost at 12 or 24 V is a large share of the total and can trip the inverter on low voltage. Most codes do not set a DC limit; the NEC suggests 3% for branch circuits in an informational note.

Is 4 mm² or 6 mm² cable better for solar panels?

4 mm² (about 12 AWG) and 6 mm² (about 10 AWG) are the standard PV cable sizes. 4 mm² is enough for most single strings over short runs. Choose 6 mm² for long runs, low-voltage systems or parallel strings, where the voltage drop on 4 mm² goes over your limit. Enter your string current and length above to check.

Sizing a series string first? Use the string sizing calculator to find how many panels fit on your inverter.